How to read a large power user electricity account

A line-by-line guide to a large power user electricity account: what each charge is built from, where errors hide, and four checks you can do yourself.

A large power user account looks like any other invoice: a list of lines, a total and a due date. The difference is what sits behind each line. Every rand on it is the product of a meter reading, a multiplier, a tariff rate and a set of rules about when each one applies. If any one of those is wrong, the total is wrong, and nothing on the page will tell you so.

This guide walks through the lines you will find on a typical account, what each one is built from, and where an error can hide. It closes with four checks you can do yourself, with nothing more than your last twelve accounts and a qualified electrician.

Layouts differ between municipalities and change over time, so the line names on your account may not match these exactly. The quantities behind them are the same.

How every charge is built

Each charge starts with a register on the meter. The register reading is multiplied by the meter multiplier to give the quantity billed. That quantity is then multiplied by the rate in the tariff that applies to your account.

An error can enter at either step:

  • In the quantity: a wrong multiplier, a register mapped to the wrong period, an estimate that was never corrected.
  • In the rate: the wrong supply category, the wrong tariff, a season applied on the wrong dates.

Keep those two steps in mind as you read down the account. For every line, the question is the same: is the quantity right, and is the right rate applied to it?

The lines, one by one

Supply category and tariff

Near the top of the account you will find the supply category, usually tied to the voltage you are supplied at, and the tariff applied to it. Everything below depends on these two entries. A wrong category applies the wrong rates to every unit and every kVA, every month, and because the error sits at the top of the account, it rarely looks wrong on any individual line.

Meter multiplier

On a large supply the meter does not see the full current. Current transformers step it down, and every reading is multiplied by their ratio to give the real quantity. A 400/5 current transformer, for example, gives a multiplier of 80. On a medium-voltage supply, a voltage transformer ratio is applied as well.

If the multiplier in the billing system does not match the transformers actually installed, every reading is wrong by a factor. That usually happens after a meter change, a supply upgrade or a capture error. The error is a multiple, not a few percent. It can run in either direction, and an account that has been under-billed is not good news: once it is found, it can be corrected retrospectively.

Energy by time of use

On a time-of-use account, energy (kWh) is recorded in separate registers for peak, standard and off-peak periods, and charged at a different rate for each. Many tariffs also change their rates by season.

Three things can go wrong here:

  • A register is mapped to the wrong period in the billing system.
  • The meter’s clock has drifted, so consumption is recorded in the wrong period.
  • A seasonal rate is applied on the wrong dates.

Each one moves units into dearer periods without changing the total kWh, which is why it is easy to miss.

Maximum demand

Maximum demand (kVA) is the highest average demand over any half-hour in the billing period. A single half-hour sets the charge for the whole month.

That makes it sensitive to three things:

  • A wrong multiplier.
  • A short spike recorded during a test, a fault or a start-up.
  • A demand register that is not reset at the end of the billing period. Last month’s peak is then billed again.

Notified maximum demand

Notified maximum demand is the capacity your account is set up for, as agreed with the municipality. Some charges are based on it rather than on what you actually used. Set too high, and you pay every month for capacity you never use. Set too low, and exceeding it can bring penalty charges. It is often set when a site is first connected and not looked at again, even after the site’s load has changed.

Reactive energy

Reactive energy (kVArh) is charged where the site’s power factor falls below the level set in the tariff. Both the metering and the threshold applied are worth checking. If the charge turns out to be correct, it is often a sign that power factor correction equipment has failed or was never sized for the site’s current load. That is an operational fix rather than a billing one, but the account is usually where it first shows.

Actual or estimated readings

Where a reading could not be taken, the month is billed on an estimate, and the estimate should be corrected once an actual reading is available. An estimate is not an error in itself. A correction that never happens, or one that is applied to the wrong period, leaves the account wrong.

Fixed and service charges

Fixed charges are billed per account or per point of supply, regardless of consumption. They are rarely questioned because they do not change from month to month. That is also why a charge for a supply point that has since been disconnected, or a charge that appears twice, can run for years.

Four checks you can do yourself

None of these needs specialist software. Each one takes an hour or less.

1. Find the multiplier. Look for the multiplier or meter factor on your account. Then ask a qualified electrician to read the ratio on the current transformer nameplates in your metering kiosk. Municipal metering enclosures are sealed, and opening one is not something to do yourself. If the two figures do not agree, stop there and ask why.

2. Line up twelve months of maximum demand. List the billed maximum demand for each of the last twelve months beside what the site was doing at the time. A high peak in a month when the plant was shut for maintenance, or a figure that repeats exactly from one month to the next, is worth a question.

3. Count the estimates. Go through the same twelve accounts and note every month billed on an estimate. Then check that each estimate was followed by a correction. Several estimates in a row, or an estimate with no correction after it, is a reason to look closer.

4. Compare notified and actual demand. Find your notified maximum demand on the account and set it against the highest actual demand over the twelve months. A large gap in either direction means the capacity on your account no longer matches the site.

When it is worth an independent check

If any of these checks turns something up, or if you cannot tell either way, that is the point at which a reconciliation against your own interval data is worth having. It is also worth having if the account has never been checked at all. Even if nothing is wrong, an independent confirmation that it is correct is something you can rely on when budgets and audits come round.

An Account Verification does this for every line on the account, twelve months back, for a fixed fee quoted before any work starts. It begins with a thirty-minute conversation at no cost, to establish whether it is worth doing for your site. If it is not, we will say so.

Book the thirty minutes

Start with thirty minutes.

A conversation, at no cost, to establish whether an Account Verification is worth doing for your site, and who would sign for it. If it is not worth doing, we will say so. No files are opened and no analysis is done until an Appointment Letter and a quotation are in place.